NERC Winter Outlook: 26 GW Added, Gas Fuel Still The Weak Point

This year NERC's seasonal risk map of North America shows no area in red. The North American Electric Reliability Corporation published its 2026-2027 Winter Reliability Assessment on 18 November. It puts no region at high risk of supply shortfalls for December to February, but marks New England, Québec, the Maritimes and SERC-East as elevated risk, and it says again that the gas supply to power plants during a long cold snap is the point where things can go wrong.

More Megawatts Than Last Winter

According to the report, peak winter demand across all assessment areas has risen by 21 GW, or 2.6%, since last winter, after a 20 GW rise the year before. NERC names data centers, large industrial loads and electrification as the drivers; 21 of its 23 assessment areas expect a higher peak. Resources grew faster: winter on-peak capacity is up 26.2 GW, or 2.4%. Batteries contributed 9.2 GW of on-peak capacity and gas-fired plant 8.7 GW, ahead of wind and solar. Retirements have nearly stopped. NERC counts under 700 MW of US thermal units of 50 MW and above retired in 2026 up to September.

Demand response has also grown, by 1.9 GW to 43.6 GW, and NERC notes that more large loads, data centers among them, now take part. The report also mentions a less comfortable kind of flexibility: grid operators in the US may ask the Department of Energy for emergency orders under Section 202(c) of the Federal Power Act that direct data centers and other large customers onto their own backup generators as a last resort.

Gas Delivery In A Long Cold Spell

NERC added 9 GW of gas-fired generation to the winter resource mix this year and, for the first time, built a gas-delivery check into its risk scenarios. Using five winters of outage data, it took the largest hourly loss of gas-only generation that owners had blamed on lack of fuel and applied it to each area. In MISO, for example, that alone is 5.5 GW. Plants that can switch to a second fuel were left out of the calculation.

New England is the clearest case. More than half of its gas-fired fleet, 9.3 GW of 17.8 GW, can run on stored fuel, but NERC recalls 2012-2013, when tanks emptied fast and frozen roads and waterways held up deliveries. In the Maritimes, heavy fuel oil stored on site at dual-fuel units is one of the tools operators count on. SERC-East, traditionally a summer-peaking area, now sees its tightest hours on January mornings. In Québec, about 1,500 MW of known outages cut into the reserve margin.

The recommendations are practical: winter readiness checklists finished before December, weatherization packages fitted before storms rather than during them, fuel surveys by the balancing authorities, and gas purchases planned around long holiday weekends, when the gas trading days close early.

For Anyone Running Standby Sets

The 202(c) passage matters to data center operators. A backup genset that the grid operator can call on during a regional emergency runs in the coldest hours of the year, at full load and possibly for days, with the fuel tank as the limit. Block heaters, coolant freeze protection, fuel that will not gel and a refill contract that still works when the roads are bad are what decide whether it starts. We wrote about the first NERC standards for data centers in October; the cooling side of standby plant is on our data center page.

Sources: NERC 2026-2027 Winter Reliability Assessment, Utility Dive